Intelligent Group
Refrigerant Digital Twin

EPA 608 + LEED EAc7 + LL97 HFC ledger

Continuous chiller refrigerant inventory with leak detection, GWP-weighted carbon equivalent, and EPA Section 608 compliance tracking. Most BMS analytics tools ignore refrigerant entirely; for ESG and LL97 reporting it's often the second-largest GHG line item after grid electricity.

Total Charge
1,710lbs
across 3 machine(s)
GWP-weighted CO₂e
1,336t CO₂e
full-charge equivalent if released
Lost (lifetime)
88lbs
all logged leak events
Action Required
1
phased-out refrigerant or threshold exceeded

Chiller fleet

Each card shows refrigerant inventory, GWP, leak rate vs EPA 608 threshold, and current alert state.

CHIL-1Watch
Trane · CenTraVac CVHE · Mechanical Room (B1) · install 2014
R-134aPhasing down
HFC-134a · GWP 1,430
Charge
850 lbs
Capacity
400 tons
CO₂e (charge)
551 t
Leak rate (1y)
0.0%/ 35% EPA
Last serviced: 2024-11-12
CHIL-2OK
York · YK Steam-Turbine · Mechanical Room (B1) · install 2017
R-410APhasing down
HFC-410A · GWP 2,088
Charge
620 lbs
Capacity
300 tons
CO₂e (charge)
587 t
Leak rate (1y)
0.0%/ 35% EPA
Last serviced: 2024-10-05
RTU-1 (Lobby)Action Required
Carrier · 48TC Rooftop · Roof · install 2008
R-22Phased out
HCFC-22 · GWP 1,810
Charge
240 lbs
Capacity
25 tons
CO₂e (charge)
197 t
Leak rate (1y)
0.0%/ 35% EPA
Last serviced: 2024-09-18
R-22 production banned 2020. Schedule retrofit to R-410A or R-32.

EPA 608 compliance ledger

Every logged leak event with cause, resolution, and certified technician sign-off. Required record-keeping under 40 CFR Part 82, Subpart F.

DateEquipmentRefrigerantLost (lbs)CauseResolutionSign-off
2024-08-15CHIL-1R-134a42Pinhole on suction tubeTube re-brazed, leak test passed.EPA-608 Universal Tech (J. Reyes, Cert# 4421-A)
2024-04-09RTU-1 (Lobby)R-2218Compressor weepTopped off (R-22 reclaimed stock); retrofit scheduled.EPA-608 Universal Tech (J. Reyes, Cert# 4421-A)
2023-06-22CHIL-1R-134a28Worn shaft sealSeal replaced.EPA-608 Universal Tech (J. Reyes, Cert# 4421-A)

Refrigerant reference

GWP and regulatory status of common refrigerants in commercial HVAC. Higher GWP = more CO₂e impact per pound released.

DesignationFormulaGWP (100yr)StatusNotes
R-22HCFC-221,810Phased outProduction banned 2020. Recovered/recycled stock only. Flag for retrofit.
R-134aHFC-134a1,430Phasing downAIM Act phase-down — retrofit to R-1234yf or R-513A planned by 2030.
R-410AHFC-410A2,088Phasing downCommon in chillers and rooftop units. AIM Act phase-down to R-32/R-454B by 2025.
R-32HFC-32675CurrentMildly flammable (A2L). Replaces R-410A in newer equipment.
R-1234yfHFO-1234yf4Low-GWPUltra-low-GWP. Standard in new chiller installs.
EPA Section 608 (40 CFR Part 82, Subpart F) sets recordkeeping and leak-repair thresholds for refrigerant equipment. AIM Act (2020) phases down HFCs by 85% by 2036; LL97 GHG inventory includes refrigerant releases at GWP × pounds released. GWP values per IPCC AR5.